Category: Products

Applications:   Low Temperature Hot Water, Condensate, Dual-Temperature, Chilled Water Service Pipe size:  1 1/2″-12″ diameter, 20′ or 40′ nominal lengths Temperature range:  35ºF to 250ºF Max. operating pressure:  150psi Carrier:  Steel Insulation:  Polyurethane foam Casing:  Heavy wall Polyvinyl Chloride (PVC, PIP80) or  High Density Polyethylene (HDPE) Options: Schedule 40/80 or ...

Applications:   Low Temperature Hot Water, Condensate, Dual-Temperature Service Pipe size:   2″-12″ diameters, 20′ or 19’ nominal length Temperature range:   35ºF to 230ºF Max. operating pressure:   150psi Carrier:   Fiberglass Reinforced Plastic (FRP) Insulation:   Polyurethane foam Casing:   Heavy wall Polyvinyl Chloride (PVC, PIP80) or High Density Polyethylene (HDPE) Options: Standard wall Polyvinyl ...

Applications:   Low Temperature Hot Water, Dual-Temperature, Chilled Water Service Pipe size:   3”- 18” diameters, 18’ or 20′ nominal lengths Temperature range:   35ºF to 250ºF Max. operating pressure:   150psi Carrier:   Ductile iron Insulation:   Polyurethane foam Casing:   Heavy wall Polyvinyl Chloride (PVC, PIP80) or High Density Polyethylene (HDPE) Options: Standard wall Polyvinyl ...

Applications:   Steam, High Pressure Return, Condensate Service Pipe size:   3″-12″ diameter, 20′ nominal lengths Temperature range:   212ºF to 406ºF Max. operating pressure:   250psi Carrier:   Steel Primary Insulation:   Calcium silicate or Foamglass® insulation Secondary Insulation:    Polyurethane foam Casing:   Heavy wall fiberglass Reinforced Thermosetting Resin Pipe Options: Schedule 40/80 or Standard/Extra ...

Applications:   Steam, High Temperature Hot Water, Condensate Service Pipe size:   1 1/2″-16″ diameter, 20′ or 40′ nominal lengths Temperature range:   250ºF to 450ºF Max. operating pressure:   250psi Carrier:   Steel Primary Insulation:   Calcium Silicate or Foamglas® insulation Secondary Insulation:   Polyurethane foam Casing:   Heavy wall fiberglass Reinforced Thermosetting Resin Pipe Options: Schedule 40/80 ...

Applications:    Low Temperature Hot Water, Condensate, Dual-Temperature Service Pipe size:   2″-12″ diameters, 19′ or 20’ nominal length Temperature range:   35ºF to 230ºF Max. operating pressure:   150psi Carrier:   Fiberglass Reinforced Plastic (FRP) Insulation:   Polyurethane foam Casing:   Heavy wall Polyvinyl Chloride (PVC, PIP80) or High Density Polyethylene (HDPE) Options: Standard wall ...

Applications:    Domestic Hot Water, Heating Hot Water, Dual-Temperature, Chilled Water Service Pipe size:   1”- 6” diameters, 20’ nominal lengths Temperature range:   35ºF to 250ºF Max. operating pressure:   150psi Carrier:   Copper (Type K or L) Insulation:   Polyurethane foam Casing:    Heavy wall Polyvinyl Chloride (PVC, PIP80) or High Density Polyethylene ...

Applications:    Low Temperature Hot Water, Condensate, Dual-Temperature, Chilled Water Service Pipe size:   1 1/2”-24” diameter, 20’ or 40’ nominal lengths Temperature range:   35ºF to 250ºF Max. operating pressure:   150psi Carrier:   Steel Insulation:   Polyurethane foam Casing:   Heavy wall Polyvinyl Chloride (PVC, PIP80) or High Density Polyethylene (HDPE) Options: Schedule 40/80 ...

Applications:    Chilled Water, Low Temperature Condenser Water Service Pipe size:   1 1/2”- 24” diameters, 20’ nominal lengths Temperature range:   35ºF to 120ºF Max. operating pressure:   150psi Carrier:   Polyvinyl Chloride (PVC) Class 160 or 200psi pipe Insulation:   Polyurethane foam Casing:   Heavy wall Polyvinyl Chloride (PVC, PIP80) or High Density Polyethylene (HDPE) ...