(1) CARRIER: FRP Pipe. (2) INSULATION: Polyurethane Foam (3) CASING: PVC or HDPE (4) ADHESIVE BOND (5) END SEAL: EPDM (6) CASING-TITE SLEEVE: PVC or HDPE (7) CASING-TITE SEAL: 30 mil High Temperature Tape NOMINAL PIPE SIZE (IN.) NOMINAL CASING SIZE (IN.) CARRIER O.D. (IN.) CASING O.D. (IN.) THICKNESS WEIGHT (LBS./ 20 FT.) FOAM (IN.) PVC CASING (IN.) 2 4 2.38 4.50 0.92 0.140 40 3 6 3.50 6.14 1.20 0.120 55 4 8 4.50 8.16 1.67 0.160 89 6 10 6.63 10.20 1.59 0.200 146 8 12 8.63 12.24 1.57 0.240 205 10 14 10.75 14.28 1.49 0.280 288 12 16 12.75 16.00 1.38 0.250 326 NOTE: Standard lengths are 20'-0". Weights are approximate. Consult manufacturer for HDPE dimensional data. SHORT FORM SPECIFICATIONS 1.1 All underground pre-insulated pipe 2” – 12” shall be Thermal Pipe Systems, Inc. Taper-Tite® piping with adhesive bonded joints. 1.2 FRP carrier pipe shall be Fiberglass Reinforced Plastic (FRP) with resin-rich liner and shall comply with ASTM D2310 and D2996. Resin Designation Codes shall be RTRP-11FX1: 3110 for all sizes. The pipe shall be suitable for use at maximum hydrostatic working pressure of 150 psi at 230ºF. 1.3 The pipe shall be joined with adhesive using matching tapered bell and spigot ends. This matching taper is designed to mechanically ‘lock’ the pipe when assembled properly, using the instructions supplied by Thermal Pipe Systems. 1.4 Casing pipe shall be [Polyvinyl Chloride (PVC) meeting the minimum classification requirements of ASTM D-1784] or [High Density Polyethylene (HDPE)]. The thickness shall be in accordance with the Thermal Pipe Systems published data. 1.5 The insulation shall be polyurethane foam completely encapsulated on each end by a compression rubber end seal. Pipe joints shall be insulated using polyurethane foam half shells and protected with a Casing-Tite Sleeve. 1.6 The rubber end seals shall be an Ethylene Propylene Diene Monomer (EPDM) heat resistant compound. 1.7 Fittings shall be uninsulated FRP designed to be used with the carrier pipe. Fittings shall have a bell to match the tapered spigot end of the pipe. The fittings shall be joined with adhesive supplied by Thermal Pipe Systems. 1.8 After completion of hydrostatic testing, joints shall be closed using factory supplied 30 mil high temperature tape. It shall be applied circumferentially around the seam between the coupling and pipe casing. WARRANTY We warrant that our products are manufactured with the applicable material specifications and are free from defects in the workmanship and material using our specifications as a standard. Every claim under this warranty shall be deemed waved unless in writing received by Thermal Pipe systems, Inc. within (30) days of the date the defect was discovered and within (1) year of the date of shipment of the product. Thermal Pipe Systems, Inc. MAKES NO REPRESENTATION OR WARRANTY OF ANY KIND, EXPRESSED OR IMPLIED, IN FACT OR IN LAW, INCLUDING WITHOUT LIMITATION THE WARRANTY OF MERCHANTABILITY OR THE WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE, OTHER THAN THE LIMITED WARRANTY SET FORTH ABOVE. LIMITATIONS AND LIABILTY It is expressly understood and agreed that the limit of Thermal Pipe Systems, Inc. liability shall be the resupply of a like quantity of nondefective product and that Thermal Pipe Systems, Inc. shall have no such liability except where the damage or claim results solely from the breach of the Thermal Pipe Systems, Inc. warranty. IT IS ALSO AGREED THAT THERMAL PIPE SYSTEMS, INC. SHALL NOT BE LIABLE FOR ANY INCIDENTAL, CONSEQUENTIAL, OR OTHER DAMAGES FOR ANY ALLEGED NEGLIGENCE, BREACH OF WARRANTY, STRICT LIABILTY OR ANY OTHER THEORY, OTHER THAN THE LIMITED LIABILTY SET FORTH. ThermalPipeSystems,Inc. 5205 W. Woodmill Dr. Suite 33 – Wilmington, DE 19808 Tel: 302-999-1588 – Fax: 302-999-8861 Website: www.thermalpipesystems.com TAPER-TITE® 230