(1) CARRIER: Ductile Iron. (2) INSULATION: Polyurethane Foam (3) CASING: PVC or HDPE (4) CARRIER SEALING RING: Rubber (5) END SEAL: Compression Rubber (6) CASING-TITE SEAL: 30 mil High Temperature Tape (optional for chilled water) NOMINAL PIPE SIZE (IN.) NOMINAL CASING SIZE (IN.) CARRIER O.D. (IN.) CASING O.D. (IN.) THICKNESS WEIGHT (LBS./20 FT.) FOAM (IN.) PVC CASING (IN.) 3 6 3.96 6.14 0.97 0.120 220 4 8 4.80 8.16 1.52 0.160 265 6 10 6.90 10.20 1.45 0.200 379 8 12 9.05 12.24 1.36 0.240 538 10 14 11.10 14.28 1.31 0.280 716 12 16 13.20 16.00 1.15 0.250 872 14 18 15.30 18.70 1.33 0.370 1159 16 22 17.40 22.05 1.90 0.430 1446 18 24 19.50 24.80 2.04 0.490 1740 NOTE: Standard lengths are 18'-0" or 20'-0". Weights are approximate. Consult manufacturer for HDPE dimensional data SHORT FORM SPECIFICATIONS 1.1 All underground pre-insulated pipe 3” – 18” shall be Thermal Pipe Systems, Inc. Duc-Tite® piping with Ring-Tite joints. 1.2 Carrier pipe shall be ductile iron pipe conforming to ANSI A21.51 and AWWA C151. Pipe shall be Class 51 in sizes 3” and 4”, and Class 50 in sizes 6” through 18”. Rubber sealing rings shall be provided with the pipe and shall be as specified under AWWA C104. The pipe shall be suitable for use at maximum hydrostatic working pressure of 150 psi at 250ºF. 1.3 Each joint shall automatically provide for expansion and contraction through the rubber sealing rings placed in the groove of the bell. Pipe and fittings must be assembled with a non-toxic lubricant supplied by Thermal Pipe Systems. 1.4 Casing pipe shall be [Polyvinyl Chloride (PVC) meeting the minimum classification requirements of ASTM D-1784] or [High Density Polyethylene (HDPE)]. The thickness shall be in accordance with the Thermal Pipe Systems published data. 1.5 The insulation shall be polyurethane foam completely encapsulated on each end by a compression rubber end seal. 1.6 The end seals shall be compression rubber. 1.7 Fittings shall be ‘push-on’ ductile iron. WARRANTY We warrant that our products are manufactured with the applicable material specifications and are free from defects in the workmanship and material using our specifications as a standard. Every claim under this warranty shall be deemed waved unless in writing received by Thermal Pipe systems, Inc. within (30) days of the date the defect was discovered and within (1) year of the date of shipment of the product. Thermal Pipe Systems, Inc. MAKES NO REPRESENTATION OR WARRANTY OF ANY KIND, EXPRESSED OR IMPLIED, IN FACT OR IN LAW, INCLUDING WITHOUT LIMITATION THE WARRANTY OF MERCHANTABILITY OR THE WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE, OTHER THAN THE LIMITED WARRANTY SET FORTH ABOVE. LIMITATIONS AND LIABILTY It is expressly understood and agreed that the limit of Thermal Pipe Systems, Inc. liability shall be the resupply of a like quantity of nondefective product and that Thermal Pipe Systems, Inc. shall have no such liability except where the damage or claim results solely from the breach of the Thermal Pipe Systems, Inc. warranty. IT IS ALSO AGREED THAT THERMAL PIPE SYSTEMS, INC. SHALL NOT BE LIABLE FOR ANY INCIDENTAL, CONSEQUENTIAL, OR OTHER DAMAGES FOR ANY ALLEGED NEGLIGENCE, BREACH OF WARRANTY, STRICT LIABILTY OR ANY OTHER THEORY, OTHER THAN THE LIMITED LIABILTY SET FORTH. ThermalPipeSystems,Inc. 5205 W. Woodmill Dr. Suite 33 – Wilmington, DE 19808 Tel: 302-999-1588 • Fax: 302-999-8861 website: www.thermalpipesystems.com DUC-TITE®